WSM3-G07 0444 - 1104

Reversible air cooled fully configurable high efficiency Rooftop units
122 - 314 kW

Stand alone reversible air-to-air Rooftop unit, for the thermo-hygrometric treatment, filtration and air renovation, in medium-large surface and volume environments (supermarkets, shopping or exhibition centres). VSD scroll compressors for sizes < 120 kW and 4 ON/OFF tandem compressors for higher capacities. Together with electronic lamination valves, these solutions allow to punctually follow the building demand, getting the highest efficiencies with relevant energy and cost savings. According to the selected version, the unit can manage the free cooling operation thanks to motorized dampers for return, exhaust and fresh air. The unit is also available with the thermodynamic and Refrigerant Booster heat recoveries, air-to air Plate type or rotary heat exchangers, to recover the energy from the exhaust air, increasing the unit capacity and the global efficiency.

Dostępny w polsce:

TAK

Contact information
Mitsubishi Electric Poland Branch
Tel: +48 22 468 27 50
Email: kontakt-les@mpl.mee.com
Website:www.mitsubishi-les.com/pl/
Address: ul. Łopuszańska 38C
Warszawa 02-232

Technical Data

WSM3-G07/AR 044404840524060407040804090410041104
Power supply V/ph/Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
COOLING ONLY (GROSS VALUE)
Total cooling capacity (1) kW 122 138 152 176 203 234 263 283 314
Total sensible capacity (1) kW 99.2 109 124 137 155 185 214 231 252
Compressor power input (1) kW
EER (total) (1) (12) kW/kW 2.7 2.7 2.7 2.9 3.1 2.7 3.1 3.1 2.7
COOLING ONLY (EN14511 VALUE)
Cooling capacity (1) (3) kW 126 141 157 181 209 241 271 291 323
EER (1) (3) kW/kW 3.02 3.01 2.96 3.16 3.4 3.01 3.4 3.4 2.99
HEATING ONLY (GROSS VALUE)
Total heating capacity (2) kW 123 143 163 174 203 241 257 276 307
Compressor power input (2) kW
COP (total) (2) (12) kW/kW 3.1 3.1 3.1 3.1 3.3 3.2 3.2 3.2 3.1
HEATING ONLY (EN14511 VALUE)
Total heating capacity (2) (3) kW 120 140 159 168 197 234 250 268 298
COP (2) (3) kW/kW 3.25 3.23 3.21 3.26 3.44 3.3 3.38 3.32 3.2
SEASONAL EFFICIENCY IN COOLING (Reg. EU 2016/2281)
Ambient refrigeration
Prated,c (7) kW 126 141 157 181 209 241 271 291 323
SEER (7) (8) 4.51 4.4 4.56 4.6 4.28 4.43 4.51 4.36 4.1
Performance ηs (7) (9) % 177.4 173 179.4 181 168.2 174.2 177.4 171.4 161
Seasonal efficiency class B B B B
SEASONAL EFFICIENCY IN HEATING (Reg. EU 2016/2281)
Ambient heating
PDesign (7) kW 90.5 106 120 127 127 171 181 195 219
SCOP (7) (8) 3.42 3.27 3.34 3.44 3.38 3.52 3.42 3.39 3.4
Performance ηs (7) (10) % 133.8 127.8 130.6 134.6 132.2 137.8 133.8 132.6 133
Seasonal efficiency class (from D to A+++) B B B B
SUPPLY FANS
Air flow rate m³/h 24,000 26,000 29,000 33,000 36,500 43,500 49,000 53,000 56,000
Nominal ESP (4) Pa 300 300 350 350 350 350 350 350 350
Total power input (12) kW 4.29 4.8 5.6 5.73 5.71 7.89 9.07 10.5 11.7
REFRIGERANT CIRCUIT
No. Compressors/No. Circuits 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
Theoretical refrigerant charge (6) (11) kg 25.2 26.8 30.7 33 57.6 57.6 62.4 62.4 74.4
NOISE LEVEL
Sound power level in cooling mode (5) dB(A) 88 91 92 91 95 95 96 96 97
Sound Power on outlet side (5) dB(A) 89 89 90 90 91 92 92 92 93
SIZE
Length A (6) mm 5,140 5,140 5,140 5,140 6,820 6,820 7,910 7,910 7,910
Width B (6) mm 2,250 2,250 2,250 2,250 2,250 2,250 2,250 2,250 2,250
Height H (6) mm 2,425 2,425 2,425 2,425 2,410 2,410 2,410 2,410 2,410
Operating weight (6) kg 2,010 2,050 2,140 2,150 2,945 2,945 3,265 3,265 3,505

Features

LOW GWP REFRIGERANT
The pure refrigerant R32 is an extraordinary eco-sustainable alternative to traditional refrigerant R410A, offering a 66% reduction in terms of GWP, a higher efficiency and a lower refrigerant charge.
HIGH EFFICIENCY AT PARTIAL LOAD
Top-level partial load efficiency, granting an effective energy and economic savings, thanks to VSD scroll compressors for sizes < 120 kW and 4 ON/OFF tandem compressors for higher capacities.
HIGH RELIABILITY
The wide working range, the inverter technologies and the tandem compressors, together with the accurate design of the components, ensure optimum performance and comfort, with a continuous and constant operation also during heavy thermoigrometric conditions.
FLEXIBILITY
The unit is available with the opportunity to choose different supply and return airflow directions and is always delivered as packaged unit with all the desired configurations.
ROTARY-TYPE ENTHALPY RECOVERY
The exclusive enthalpic rotary heat recovery recovers both sensible and latent heat from the exhaust air, in winter and summer operation. The recovery of the latent heat improves the dehumidification capability of the unit in summer and the humidification in winter, with a very high efficiency ratio.
STATIC PLATE HEAT RECOVERY
The static plate heat recovery provides a constant and effective recovery of the sensible energy from the exhaust air, keeping always the supply and the return airflows separated. In winter mode the efficiency can reach high values, that, together with the zero energy consumption of the component, grant an effective energy and economic saving.
REFRIGERANT BOOSTER
Cutting-edge Refrigerant booster heat recovery system that completely and precisely recovers of the energy from the exhaust air, without any waste due to the mixing with external air. The performance of the cooling circuit is maximized, increasing the cooling capacity by 15% and the compressor working at the same condition.
VARIABLE AIRFLOW FUNCTION
Thanks to the advanced logics of AIR3000+, the Variable Airflow Function allows to adjust the supply and the return airflows according to the real plant demand, granting an important reduction (up to 30%) of annual energy consumption.

Configurtions

AR Air recirculation function
MF Mixing and Free cooling function
AX-F Mixing and Free cooling and extraction fan with thermodynamic heat recovery from exhaust air flow
HR-F Heat Recovery Free: air extractor fan(s), free cooling function and thermodynamic heat recovery from exhaust air flow
HR-B Heat Recovery Refrigerant Booster function: air extractor fan(s), free cooling function and heat recovery from exhaust air flow thanks to Refrigerant Booster coil
HR-P Heat Recovery Plate function: air extractor EC plug fan(s), free cooling function, and heat recovery from exhaust air flow thanks to Plate (cross-flow) heat exchanger.
HR-E Heat Recovery Enthalpy function: air extractor EC plug fan(s), free cooling function and heat recovery from exhaust air flow thanks to Rotary Enthalpic Wheel.

Accessories

KIPlink user interface
High efficiency filters: electronic or bag type ePM01 50% (ISO16890, F7 EN779) or ePM01 85% (ISO16890, F9 EN779)
Enthalpy free-cooling
CO2 control sensor for air quality
Vair: variable air flow function, it varies supply and return air flow according to the actual request of the HVAC system.

Controls

AIR3000+

AIR3000+ with LCD display is made up by two control boards, dedicated to the air side and the refrigerant side respectively. The management of the thermoregulation is proportional or proportional + integral, referring to the return temperature. Its functions include the adjustment of the ambient humidity, the thermal or enthalpic (optional) free-cooling and supply temperature limitation. Defrosting is based on a self-adaptive propriety logic with monitoring of several operating and environmental parameters. The management of the ventilation can be realized with constant air flow or pressure regulation: as pressure drop varies, the fans change speed so as to maintain the flow-rate at the designed value. The new VAIR function (variable airflow) allows to adjust the supply and the return airflows according to the real plant demand. The controller independently manages several optional thermal resources as well as the amount of fresh air, with the possibility to create different operating profiles. Supervision can be developed via third party systems by means of the most common protocols as ModBus, Bacnet, Bacnet-over-IP, ModBus-over-IP, Echelon protocols. Compatibility with the remote keyboard managing up to 8 units.

Downloads